Schneider Electric

Switch actuator REG‐K/ x230/16 with manual mode

  • Sale
  • Please log in to see prices or make an order


For independent switching of loads via make contacts. With integrated bus coupler and screw terminals. The 230 V switch output can be operated with a manual switch.
A green LED indicates readiness for operation after the application has been loaded.
For installation on DIN rails TH35 according to EN 60715. The bus is connected using a bus connecting terminal; a data rail is not necessary.

KNX software functions: Operation as break or make contact, delay functions for each chan- nel, staircase lighting function with/without manual OFF function, cut-out warning for staircase lighting function, blocking and additional logic operation or priority control, scenes, status feedback function per channel, central function, comprehensive parameterisation for bus volt- age failure and recovery, parameterisable download behaviour.

Nominal voltage: AC 100-240 V ±10%
Operating voltage: min. AC 90 V - max. AC 265 V
Mains frequency: 50-60 Hz ±10%
For each switching contact:
Switching current: 16 A, cosφ= 0.6
AC1 operation: max. 16 A
AC3 operation: max. 10 A
AC5 operation: max. 16 A
DC current switching capacity: max. 16 A/ 24 V DC
Output life endurance:
Mechanical: >106
AC1/AC3/AC5 operation: >3x104
230V, 1A resistive: >8x105
Nominal load
Incandescent lamps: AC 100 V, max. 1600 W
AC 230 V, max. 3600 W
AC 240 V, max. 3840 W
Halogen lamps: AC 100 V, max. 1086 W
AC 230 V, max. 2500 W
AC 240 V, max. 2608 W
Fluorescent lamps: AC 100 V, max. 1086 VA
AC 230 V, max. 2500 VA
AC 240 V, max. 2608 VA
parallel-compensated
Capacitive load: AC 230 V, 16 A, max. 200 μF
Minimum switching performance: 100 mA/12 V AC/DC Maximum peak inrush‐current:
150μs: 600 A
250μs: 480 A
600μs: 300 A

Contents: With bus connecting terminal and cable cover.