siemens

Switching actuators N53x/

  • Sale
  • Please log in to see prices or make an order


Rated contact current according to DIN EN 60669:
6 AX (70 µF fluorescent lamp load), 10 A (resistive load)
10 AX (140 µF fluorescent lamp load), 10 A (resistive load)
16 AX / 20 AX (200 µF fluorescent lamp load)
  • One relay contact per output as switching element
  • Rated contact operating voltage AC 230 V
  • Rated contact frequency: 50/60 Hz
  • Per output with mechanical display of the switching status via slide switches, which can also be used for direct manual operation of the switching output
  • Maintenance-free terminals for connection and through-wiring of untreated single-core, stranded or multi-core conductors, 0.5 ... 2.5 mm²
  • One phase terminal per output
  • Bus-powered electronics
  • Integrated bus coupling unit, bus connection via bus terminal block
  • Red LED for display of the activation of the addressing mode as well as the operational readiness
  • Housing: plastic, color RAL 7035 (light grey), N-system
  • DIN rail mounted device for mounting on rail TH35 according to DIN EN 60715
  • Type of protection: IP 20
Additional functionalities GAMMA
Per output
  • Selectable operating mode (normal mode, time switch mode, flashing mode)
  • Selectable relay mode (NC/NO)
  • Variable On and Off delay times
  • Two selectable logic operations (AND, OR, NAND, NOR, XOR, FILTER, TRIGGER)
  • Selectable sending of status objects on request, cyclically and/or automatically after a change
  • Selectable switching state on bus voltage failure
  • Selectable start value of the switching object on bus voltage recovery
  • Optional addition of a night mode object for time-limited switching On of the output, i.e. the illumination, at night
  • Variable On period at night or time switch mode
  • Selectable addition of an object to change the On period at night or time switch mode
  • Selectable post-triggering (1x, 2x, 3x, 4x, 5x) of the On period in time switch mode
  • Selectable warning signal prior to imminent switching-off by brief off and on switching (flashing) at night or in time switch mode and/or via an optional warning object

Per output selectable functions:
  • For manual override ON
  • For permanent OFF switching
  • Blocking of the output
  • For switching on or off in forced mode
  • Counting of operating hours and threshold monitoring
  • Counting of load cycles and threshold monitoring
  • Integrated 8-bit scene control with up to 8 scenes per output

  • Construction site function switching
  • Object for monitoring of device function
  • Object for targeted retrieval of status values

 

Detailed information

ETS Datafile (4 outputs units)

ETS Datafile (8 outputs units)

ETS Datafile (12 outputs units)