For generating the bus voltage for a line with up to 64 bus devices.
With integrated choke to decouple the power supply from the bus and a push-button to disconnect the power and reset the bus devices connected to the line.
The emergency power supply REG can be connected in order to buffer the bus voltage.
For installation on DIN rails TH35 according to EN 60715. The bus is connected using a bus connecting terminal; a data rail is not necessary.
Nominal voltage: AC 110-230 V ±10%
Operating voltage: min. AC 92 V - max. AC 253 V
Mains frequency: 50-60 Hz ±10%
Output voltage: DC 30 V
Output current: short-circuit- proof
Device width: 4 TE = approx. 72 mm
Output voltage: DC 30 V
Output current: short-circuit- proof
Device width: 4 TE = approx. 72 mm
Contents: With bus connecting terminal and cable cover.