Rated contact current according to DIN EN 60669:
- 6 AX (70 µF fluorescent lamp load), 10 A (resistive load)
- 10 AX (140 µF fluorescent lamp load), 10 A (resistive load)
- 16 AX / 20 AX (200 µF fluorescent lamp load)
- One relay contact per output as switching element
- Rated contact operating voltage AC 230 V
- Rated contact frequency: 50/60 Hz
- Per output with mechanical display of the switching status via slide switches, which can also be used for direct manual operation of the switching output
- Maintenance-free terminals for connection and through-wiring of untreated single-core, stranded or multi-core conductors, 0.5 ... 2.5 mm²
- One phase terminal per output
- Bus-powered electronics
- Integrated bus coupling unit, bus connection via bus terminal block
- Red LED for display of the activation of the addressing mode as well as the operational readiness
- Housing: plastic, color RAL 7035 (light grey), N-system
- DIN rail mounted device for mounting on rail TH35 according to DIN EN 60715
- Type of protection: IP 20
Per output
Per output selectable functions:
- Selectable operating mode (normal mode, time switch mode, flashing mode)
- Selectable relay mode (NC/NO)
- Variable On and Off delay times
- Two selectable logic operations (AND, OR, NAND, NOR, XOR, FILTER, TRIGGER)
- Selectable sending of status objects on request, cyclically and/or automatically after a change
- Selectable switching state on bus voltage failure
- Selectable start value of the switching object on bus voltage recovery
- Optional addition of a night mode object for time-limited switching On of the output, i.e. the illumination, at night
- Variable On period at night or time switch mode
- Selectable addition of an object to change the On period at night or time switch mode
- Selectable post-triggering (1x, 2x, 3x, 4x, 5x) of the On period in time switch mode
- Selectable warning signal prior to imminent switching-off by brief off and on switching (flashing) at night or in time switch mode and/or via an optional warning object
Per output selectable functions:
- For manual override ON
- For permanent OFF switching
- Blocking of the output
- For switching on or off in forced mode
- Counting of operating hours and threshold monitoring
- Counting of load cycles and threshold monitoring
- Integrated 8-bit scene control with up to 8 scenes per output
- Construction site function switching
- Object for monitoring of device function
- Object for targeted retrieval of status values